Type HSR Pressure Regulators for Residential, Commercial, or Industrial Applications
Regulator Return Program
July 10, 2007
Fisher
Controls, Regulator Division is requesting the return of regulators per the
July 10, 2007 IMPORTANT SAFETY NOTICE--REGULATOR RETURN. The regulators
to be returned are the Type/Series HSR, 67C, 67CR, 67CF, 67CFR, and R622.
Natural Gas, Industrial Processes, and Air — Safety
Notice
The Type HSR direct-operated, spring-loaded pressure regulators provide economical pressure reducing control in a variety of residential, commercial, and industrial applications. The Type HSR pressure regulators can be used with natural, manufactured, or liquefied petroleum gases. In addition, the Type HSR pressure regulators have internal relief across the diaphragm to help minimize overpressure. Any outlet pressure above the start-to-discharge point of the nonadjustable relief valve spring moves the diaphragm off the relief valve seat, allowing excess pressure to bleed out through the screened spring case vent.
The Type HSR pressure regulators meet ANSI B109.4 / CGA 6.18.
Body Size and End Connection Styles
3/4 x 3/4-inch (DN 20 x 20)
3/4 x 1-inch (DN 20 x 25)
1 x 1-inch (DN 25 x 25) NPT
All sizes available in Globe or Angle Body
Allowable Outlet Pressure
Emergency (Casing): 25 psig (1,7 bar)
Maximum Operating Pressure to Avoid Internal Parts Damage: 3 psi (0,21 bar) differential above outlet pressure setting
Outlet Pressure Ranges
4-inches w.c. to 2.2 psig (10 mbar to 0,15 bar) in 7 ranges
Temperature Capabilities
-20° to 160°F (-29° to 71°C)
Additional Technical Data
For additional technical information,
contact your Local Sales Office or refer to technical documentation.